Ecophon Hygiene™ Meditec A

Suitable application areas are hospitals: patient, treatment or examination rooms. Ecophon Hygiene Meditec A has an exposed grid system. Each tile is demountable.
SYSTEM RANGE
Size, mm
600
X
600

1200
X
600
T24
Thickness 15 15
Inst. diagr. m90 m90

The system consists of Ecophon Hygiene Meditec A tiles and Ecophon Connect grid systems, with an approximate weight of 2,5 kg/m². The tiles are manufactured from high density glass wool. The visible surface has a reinforced Akutex T coating that can withstand the use of disinfecting chemicals. The back of the tile is covered with glass tissue. The edges are primed. The grid is manufactured from galvanized steel.

SOUND ABSORPTION: Test results according to EN ISO 354.
Classification according to EN ISO 11654, and the single value ratings for NRC and SAA according to ASTM C 423.
SOUND INSULATION: Not applicable.
SOUND PRIVACY: Not applicable.

αp Practical sound absorption coefficient
<em>α</em><sub>p</sub> Practical sound absorption coefficient
Frequency, Hz
Ecophon Hygiene Meditec A 200 mm o.d.s.
···Ecophon Hygiene Meditec A 50 mm o.d.s.
o.d.s = overall depth of system

Product Hygiene Meditec A
O.d.s. mm 400 200 50
Absorption class   A C
NRC 0.85   0.8
SAA 0.88   0.83

Meditec A tile
Section of Meditec A system
Meditec A system
Manual wet cleaning of Meditec A
ACCESSIBILITY: The tiles are demountable. Minimum demounting depth according to installation diagram.
CLEANABILITY: Daily dusting and vacuum cleaning. Weekly wet cleaning. Can withstand the use of common disinfecting chemicals.
LIGHT EFFICIENCY: White 010, nearest NCS colour sample S 0502-Y, 84% light reflectance (of which more than 99% is diffuse reflection).
INFLUENCE OF CLIMATE: The tiles withstand a permanent ambient RH up to 95% at 30°C without sagging, warping or delaminating (ISO 4611).
INDOOR CLIMATE: Certified by the Indoor Climate Labelling, recommended by the Swedish Asthma and Allergy Association, and can be used in rooms classified as ISO class 5/M2.5.
ENVIRONMENTAL INFLUENCE: Granted the Nordic Swan eco-label. Fully recyclable.
FIRE SAFETY: Reaction-to-fire classifications.
Country Standard Class
UK BS 476 Parts 6&7 Class 0
Europe EN 13501-1 A2-s1,d0
The glass wool core of the tiles is tested and classified as non-combustible according to prEN ISO 1182. The system is classified as fire protective covering according to NT FIRE 003. See Functional demands, Fire safety.
MECHANICAL PROPERTIES: For information regarding live load and requirements for load bearing capacity, see installation diagram. Conditions: See Functional demands, Mechanical properties.
Inst. diagr., Size (mm) Max live load (N) Min load bearing capacity (N)
m90, 1200x600 50 160
m90, 600x600 50 160
INSTALLATION: Installed according to installation diagram M90, which includes information regarding minimum overall depth of system. Cut edges must be sealed with Connect Edge paint 0690. Penetrations must be sealed with Connect Hygiene sealant 0041.
www.ecophon.com, CADsupport, Product selector, Specification, Maintenance manual
 To top
Quantity specification (excl. wastage)
Installation diagram (M90) for Meditec A
Size, mm
600x600 1200x600
Hygiene Meditec A 2.8/m² 1.4/m²
1 Connect T24 Main runner, installed at 1200 mm centres 0.9 m/m² 0.9 m/m²
2 Connect T24 Cross tee, L=1200 1.7 m/m² 1.7 m/m²
3 Connect T24 Cross tee, L=600 0.9 m/m² -
4 Connect Adjustable hanger, installed at 1200 mm centres (max. distance from wall 600 mm) 0.7/m² 0.7/m²
5 Connect Hanger clip 0.7/m² 0.7/m²
6 For direct installation without clip: Connect Direct bracket, installed at 1200 mm centres 0.7/m² 0.7/m²
7 Connect Universal clip 0083 11/m² 7/m²
8 Connect Angle trim, fixed at 300 mm centres as required as required
9 Connect Shadow-line trim, fixed at 300 mm centres as required as required